Estimated Lead Time: 6 - 8 Weeks
Manufacturer: GE Multilin
Product Number: 889-E-P1-P1-G1-L-S-S-A-N-N-G-M-S-F-B-1E-C-N-B-N
Product Type: Generator Protection
889 - Base Unit: Generator Protection Relay (Standard : English Language; High Voltage PS, Graphical Control Panel)
E - Language: English
P1 - Phase Currents - Slot J Bank 1: 1A three-phase currents (J1) with voltage (J2)
P1 - Phase Currents - Slot K Bank 1: 1A three-phase currents (K1) with voltage (K2)
G1 - Ground Currents: 1A ground current (qty 1 per phase current bank)
L - Power Supply: 24 - 48 VDC
S - Slot B - LV I/O: 6 x RTDs (Pt100, Ni100, Ni120, Cu10)
S - Slot C - LV I/O: 6 x RTDs (Pt100, Ni100, Ni120, Cu10)
A - Slot F - HV I/O: 2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/Ext supply)
N - Slot G - HV I/O: None
N - Slot H - HV I/O: None
G - Faceplate: Color Graphical Display
M - Current Protection: Standard = 38(RTD), 39(AnIp), 46 (Gen. Unbl.), 49 (RTD), 50/27, 50OFL, 50OL, 50P, 50N, 50G, 50SG, 50_2, 51V, 51N, 51G, 51SG, 67N, 67G, 67SG, 76 (AnIp), 87G
S - Voltage Monitoring & Protection: Standard =24, 25, 27TN, 27P, 27X, 32, 40Q, 40, 47, 59X, 81O, 81U
F - Control: Standard = Setpoint Group Control, Virtual Inputs control, Trip Bus, Flexlogic, VTFF, 50BF, Sequential shutdown, Field breaker discrepancy, Breaker control
B - Monitoring: Basic = Breaker Coils and Arcing Monitoring, Demand, Digital Counters, Running hours
1E - Communications: Advanced = Front USB, 1 x Rear RS485 + 2 x Ethernet Fiber, MODBUS RTU / TCP, DNP3.0, IEC 60870-5-103/104, 1588, SNTP, OPC UA
C - Advanced Communications Connector: RJ45, Copper 10/100M
N - Wireless Communication: None
B - Security: Basic
N - Not stated
Shipping Weight: 7 kg