Power supply unit - QUINT-PS-100-240AC/24DC/10/EX - 2938866
Degree of protection : IP20
Ambient temperature (operation) : -25 °C ... 60 °C
Ambient temperature (storage/transport) : -40 °C ... 85 °C
Max. permissible relative humidity (operation) : 100 % (condensation permitted)
Noise immunity : EN 61000-6-2:2005
Nominal input voltage range : 100 V AC ... 240 V AC
Input voltage range : 85 V AC ... 264 V AC || 90 V DC ... 250 V DC
AC frequency range : 45 Hz ... 65 Hz
Frequency range DC : 0 Hz
Current consumption : approx. 2.4 A (120 V AC) || 1.3 A (230 V AC)
Nominal power consumption : 240 W
Inrush surge current : < 15 A (typical)
Power failure bypass : > 40 ms (120 V AC) || > 40 ms (230 V AC)
Input fuse : 6.3 A (slow-blow, internal)
Choice of suitable circuit breakers : 10 A ... 16 A (Characteristics B, C, D, K)
Nominal output voltage : 24 V DC ±1 %
Setting range of the output voltage (USet) : 22.5 V DC ... 28.5 V DC
Nominal output current (IN) : 10 A (up to 60°C)
POWER BOOST (IBoost) : 15 A
Derating : 60 °C ... 70 °C (2.5%/K)
Connection in parallel : Yes, for redundancy and increased capacity
Connection in series : Yes
Residual ripple : < 100 mVPP
Output power : 240 W
Typical response time : < 1 s
Maximum power dissipation in no-load condition : 4 W
Power loss nominal load max. : 33 W
Operating voltage display : Green LED
Efficiency : > 88 %
Insulation voltage input/output : 4 kV AC (routine test) || 2 kV AC (type test)
Protection class : I
MTBF (IEC 61709, SN 29500) : > 500000 h
Mounting position : horizontal DIN rail NS 35, EN 60715
Assembly instructions : Can be aligned: Horizontally 0 mm, vertically 50 mm
Connection method : Pluggable screw connection
Conductor cross section solid min. : 0.2 mm²
Conductor cross section solid max. : 2.5 mm²
Conductor cross section flexible min. : 0.2 mm²
Conductor cross section flexible max. : 2.5 mm²
Conductor cross section AWG min. : 24
Conductor cross section AWG max. : 12
Stripping length : 7 mm
Screw thread : M3
Connection method : Pluggable screw connection
Conductor cross section solid min. : 0.5 mm²
Conductor cross section solid max. : 16 mm²
Conductor cross section flexible min. : 0.5 mm²
Conductor cross section flexible max. : 10 mm²
Conductor cross section AWG min. : 20
Conductor cross section AWG max. : 6
Stripping length : 7 mm
Screw thread : M4
Output name : DC OK active
Output description : UOUT > 0.9 x UN: High signal
Maximum switching voltage : = 24 V
Output voltage : + 24 V DC (Signal)
Maximum inrush current : max. 44 mA
Continuous load current : = 40 mA
Status display : "DC OK" LED green
Note on status display : UOUT < 0.9 x UN: LED flashing
Conductor cross section solid min. : 0.5 mm²
Conductor cross section solid max. : 16 mm²
Conductor cross section flexible min. : 0.5 mm²
Conductor cross section flexible max. : 10 mm²
Conductor cross section AWG min. : 20
Conductor cross section AWG max. : 6
Screw thread : M4
Output name : DC OK floating
Output description : Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage : = 30 V AC/DC
Maximum inrush current : = 1 A
Continuous load current : = 1 A
Status display : "DC OK" LED green
Electromagnetic compatibility : Conformance with EMC directive 89/336/EC
Standards/regulations : EN 60079-0
Noise emission : EN 55011 (EN 55022)
Noise immunity : EN 61000-6-2:2005
Connection in acc. with standard : CUL
Standard - Safety of transformers : EN 61558-2-17
Standard - Electrical safety : EN 60950-1/VDE 0805 (SELV) || EN 61558-2-17
Standard - Electronic equipment for use in electrical power installations and their assembly into electrical power installations : EN 50178/VDE 0160 (PELV)
Standard - Safe isolation : DIN VDE 0100-410
Standard – Limitation of mains harmonic currents : EN 61000-3-2
Standard - Equipment safety : GS (tested safety)
Declaration of conformity in acc. with EN 60079-15 : ? II 3 G Ex nAC IIC T4 X
Shipbuilding approval : Germanischer Lloyd (EMC 2)
UL approvals : UL/C-UL listed UL 508 || UL/C-UL Recognized UL 60950 || UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Information technology equipment - safety (CB scheme) : CB Scheme
ATEX : II 3 G Ex nA nC IIC T4 Gc X
Dimensions (LxWxH) : 12.5cm x 8.5cm x 13cm
Weight : 1.5 Kg
Shipping Weight : 2.5 Kg